Al/XLPE/Cts/PVC, Power Cable, 3.6/6 (7.2) Kv, 3/C (IEC 60502-2)
Jiangsu Boan Cable Co., Ltd.- Application:Underground, Industrial, Power Station
- Voltage:Low and Medium Voltage Cable
- Current:DC Cable
- Insulation Material:XLPE
- Sheath Material:PVC
- Material Shape:Round Wire
Base Info
- Model NO.:AL,XLPE,CTS,PVC
- Wire Core Material:Aluminum
- Certification:ISO, CCC
- Model:Al,XLPE,Cts,PVC
- Brand:Boan
- Rated Voltage:3.6,6 (7.2) Kv
- Number of Cores:3
- Class of Conductor:2
- Size:25-400 mm2
- Transport Package:Heated Steel-Wooden Drum,Steel Drum
- Specification:SGS
- Trademark:DingAn
- Origin:Jiangsu Yixing, China
- HS Code:8544601200
- Production Capacity:12000 Km,Year
Description
Basic Info.
Model NO. AL/XLPE/CTS/PVC Wire Core Material Aluminum Certification ISO, CCC Model Al/XLPE/Cts/PVC Brand Boan Rated Voltage 3.6/6 (7.2) Kv Number of Cores 3 Class of Conductor 2 Size 25-400 mm2 Transport Package Heated Steel-Wooden Drum/Steel Drum Specification SGS Trademark DingAn Origin Jiangsu Yixing, China HS Code 8544601200 Production Capacity 12000 Km/YearProduct Description
AL/XLPE/CTS/PVC, Power Cable, 3.6/6(7.2) KV, 3/C (IEC 60502-2)The cable design conforms to IEC 60502 part 2. However if requested, we can separately offer guaranteed technical particulars for cables as per different international specifications or specific customer needs.
CONSTRUCTIONAL FEATURES
Conductor
Aluminum Conductors upto 1000 sq mm will be circular compacted & stranded and shall comply with IEC-60228 Class 2.
Conductor screen
This will be an extruded layer of semiconducting XLPE applied under simultaneous triple extrusion process over the conductor along with the insulation and the insulation screen.
Insulation
This will be an extruded layer of insulating grade XLPE applied over conductor screen under triple extrusion process along with conductor screen and insulation screen.
Insulation screen
This will be a layer of semiconducting XLPE which will be applied by tripe extrusion process over the insulation.
Metallic screen
It will consist of a layer of copper tape applied helically with overlap over insulation screen. Other combinations of metallic screens as per customer's requirement can also be provided on request.
Outer sheath
An extruded layer is applied over the armour in case of armoured cables and over the laid up cores in case of unarmoured cables. Outer sheath material can be either PVC of grade ST2 or PE of grade ST7 as per IEC-60502 Part 2.
Section | Conductor diameter | Conductor weight | Insulation thickness | Outer sheath thickness | Cable overall diamete | Cable weight | Minimum bending radius of cable (During installation) | DC resistance of conductor at 20 °C (Maximum) |
mm2 | mm | kg/km | mm | mm | mm | kg/km | mm | ohm/km |
25 | 5.9 | 203 | 2.5 | 2.1 | 34.5 | 1100 | 518 | 1.20 |
35 | 6.9 | 280 | 2.5 | 2.1 | 36.5 | 1260 | 548 | 0.868 |
50 | 8.1 | 381 | 2.5 | 2.2 | 39.0 | 1480 | 585 | 0.641 |
70 | 9.7 | 553 | 2.5 | 2.3 | 43.0 | 1815 | 645 | 0.443 |
95 | 11.4 | 764 | 2.5 | 2.5 | 47.0 | 2230 | 705 | 0.320 |
120 | 12.9 | 965 | 2.5 | 2.6 | 50.5 | 2595 | 758 | 0.253 |
150 | 14.3 | 1186 | 2.5 | 2.7 | 53.5 | 2975 | 803 | 0.206 |
185 | 16.0 | 1500 | 2.5 | 2.8 | 57.5 | 3490 | 863 | 0.164 |
240 | 18.4 | 1967 | 2.6 | 3.0 | 63.5 | 4315 | 953 | 0.125 |
300 | 20.6 | 2445 | 2.8 | 3.2 | 69.5 | 5185 | 1043 | 0.100 |
400 | 23.3 | 3126 | 3.0 | 3.4 | 78.0 | 6500 | 1170 | 0.0778 |