11kv, Power Cable, XLPE Insulated, Copper Wire Screen, Swa, PVC, 1X630mm2
YIFANG ELECTRIC GROUP INC.- Application:Construction, Underground, Industrial, Power Station
- Voltage:Low and Medium Voltage Cable
- Current:AC Cable
- Insulation Material:XLPE
- Sheath Material:PVC
- Material Shape:Round Wire
Base Info
- Model NO.:yjv 1x630mm2
- Wire Core Material:Bare Copper Wire
- Certification:ISO, CCC, CE, RoHS, VDE, SABS
- Model:YJV
- Brand:Yifang Cable
- Sectional Area:630mm2
- Cores Number:1
- Insulation:XLPE
- Armor:Swa(Steel Wire Armor) or Sta(Steel Tape Armor)
- Outer Sheath:PVC
- Alternative Application:Underground
- Transport Package:Wooden Drum
- Specification:ISO CE SABS
- Trademark:Zhengzhou Yifang Cable Co., Ltd.
- Origin:Henan, China
- HS Code:8544492100
- Production Capacity:300km,Month
Description
Basic Info.
Model NO. yjv 1x630mm2 Wire Core Material Bare Copper Wire Certification ISO, CCC, CE, RoHS, VDE, SABS Model YJV Brand Yifang Cable Sectional Area 630mm2 Cores Number 1 Insulation XLPE Armor Swa(Steel Wire Armor) or Sta(Steel Tape Armor) Outer Sheath PVC Alternative Application Underground Transport Package Wooden Drum Specification ISO CE SABS Trademark Zhengzhou Yifang Cable Co., Ltd. Origin Henan, China HS Code 8544492100 Production Capacity 300km/MonthProduct Description
Structure:Rating voltage:11kV
Conductor:Cu or Aluminum
Insulation:XLPE
CWS:copper wire screen
CTS:copper tape screen
Inner sheath:PVC
SWA:steel wire armour
outer sheath:PVC(RED Color)
1. High quality
2. Competitive price
3. Fast delievery
4. Best serivce
Power cables for power networks, underground, outdoors and in cable ducting. In particular for installation where fire, smoke emission and toxic fumes create a potential threat.
Standards:
BS7835
Conductor:
Class 2 stranded plain copper conductor to BS EN 60228: 2005 (previously BS6360)
Conductor screen: Semi-conducting material
Insulation: XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
Insulation Screen:
Semi-conducting material
Metallic Screen:
Individual and overall copper tape screen to BS6622
Filler
PETP (Polyethylene Terephthalate) fibres
Separator:
Binding tape
Bedding:
LSZH (Low Smoke Zero Halogen)
Armouring: Single Core: Aluminium Wire Armoured (AWA)
MultiCore: Steel Wire Armoured (SWA)
Sheath:
LSZH (Low Smoke Zero Halogen
Voltage Rating: 6350/11000V
Temperature Rating:
0° C to +90° C Combustion CharacteristiOxygen index: 35
Temperature index: 280° HCl emission: 0.5% in accordance with BS EN 50267-2-1
Low smoke classification based on 3 metre cube test
Completed cables comply with the requirements of fire test BS4066-3 Category 3
Minimum Bending Radius: Single Core: 15 x overall diameter
Three Core: 12 x overall diameter
(Single Core 12 x overall diameter and 3 core 10 x overall diameter where bands are positioned adjacent.
Direct factory, welcome your inquiry!
1KV, 11KV XLPE insulated Armoured PVC sheathed Power Cable Hot sell
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 20ºC(Ω/km) |
3x25mm 2 | 3.4 | 0.10 | 2.2 | 40.9 | 0.727 |
3x35mm 2 | 3.4 | 0.10 | 2.3 | 43.3 | 0.524 |
3x50mm 2 | 3.4 | 010 | 2.4 | 45.9 | 0.387 |
3x70mm 2 | 3.4 | 0.10 | 2.5 | 49.8 | 0.268 |
3x95mm 2 | 3.4 | 0.10 | 2.6 | 53.6 | 0.193 |
3x120mm 2 | 3.4 | 0.10 | 2.7 | 56.8 | 0.153 |
3x150mm 2 | 3.4 | 0.10 | 2.8 | 60.6 | 0.124 |
3x185mm 2 | 3.4 | 0.10 | 2.9 | 64.3 | 0.0991 |
3x240mm 2 | 3.4 | 0.10 | 3.1 | 69.9 | 0.0754 |
3x300mm 2 | 3.4 | 0.10 | 3.3 | 74.6 | 0.0601 |
3x400mm 2 | 3.4 | 0.10 | 3.5 | 82.2 | 0.0470 |